Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 23, 2020, 08:40 AM
  • 02 1386_H JOINT _06232020_014502.mp4

Date
06/23/2020
W/O
833859
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00242
PipeID
P25322
Time
1:40 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7739
Sewer Name
CLOVERLAWN TRUNK
City
PARAMOUNT
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
31
Purpose
Routine Assessment
Project
WO_833859_TV02041_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
02 1386
Downstream MH
H JOINT
Dir. of Survey
Downstream
Length Surveyed
44.9 ft.
Total Length
44.9 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 02 1386 to H JOINT
MH: 02 1386MH: H JOINTdownstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13860 ft. MWM - Water Mark, 15 %of cross sectional area2.7 ft. MMC - Material Change, Cast Iron2.8 ft. DAE - Deposits Attached Encrustation, 20 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start2.8 ft. SCP - Surface Corrosion Metal Pipe, from 07 to 05 o'clock, within 8 inches of joint: YES, Start12.6 ft. DAE - Deposits Attached Encrustation, 20 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish12.6 ft. SCP - Surface Corrosion Metal Pipe, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish12.7 ft. MMC - Material Change, Vitrified clay pipe44.9 ft. AMH - Downstream Manhole, Survey Ends - H JOINT

Observation photos (4)

  • Material Change, Cast Iron

    2.7 ft. - Material Change, Cast Iron

  • Deposits Attached Encrustation, 20 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES, Start

    2.8 ft. - Deposits Attached Encrustation, 20 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start

  • Surface Corrosion Metal Pipe, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Corrosion Metal Pipe, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Material Change, Vitrified clay pipe

    12.7 ft. - Material Change, Vitrified clay pipe

Observations (10)

DistanceCodeObservation
2.8DAE
2.8SCP
12.6DAE
12.7MMC
0MWL
12.6SCP
0AMH02 1386
2.7MMC
0MWM
44.9AMHH JOINT

Properties (8)

additional_info
SC411398
custom_field_three
CORROSION METAL PIPE
custom_field_two
3
customer
1
datetime
2020-06-23T01:40:12-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
38576