- Date
- 06/23/2020
- W/O
- 833859
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00242
- PipeID
- P03907
- Time
- 12:01 AM
- Certificate
- U-508-7069
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K7739
- Sewer Name
- CLOVERLAWN TRUNK
- City
- PARAMOUNT
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 31
- Purpose
- Routine Assessment
- Project
- WO_833859_TV02041_JUN2020
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 8 in.
- Width
- 27 in.
- Upstream MH
- 02 1388
- Downstream MH
- 02 1389
- Dir. of Survey
- Upstream
- Length Surveyed
- 7.2 ft.
- Total Length
- 7.2 ft.
- Structural Index
- 3
- Structural Quick
- 4131
- Structural Rating
- 8
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 8
Pipe schematic from manhole 02 1388 to 02 1389 Observation photos (4)

4.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

6.8 ft. - Joint Offset Medium

7.2 ft. - Survey Abandoned - CAM BLKD BY OFFSET JOINT

7.2 ft. - Water Level, Sag in pipe, 90 %of cross sectional area