- Date
- 06/23/2020
- W/O
- 833859
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00242
- PipeID
- P03905
- Time
- 12:26 AM
- Certificate
- U-508-7069
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K7739
- Sewer Name
- CLOVERLAWN TRUNK
- City
- PARAMOUNT
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 31
- Purpose
- Routine Assessment
- Project
- WO_833859_TV02041_JUN2020
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 8 in.
- Width
- 24 in.
- Upstream MH
- 02 1387
- Downstream MH
- 02 1386
- Dir. of Survey
- Downstream
- Length Surveyed
- 340.7 ft.
- Total Length
- 340.7 ft.
- Structural Index
- 3
- Structural Quick
- 413M
- Structural Rating
- 220
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 220
Pipe schematic from manhole 02 1387 to 02 1386 Observation photos (5)

5.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

30.8 ft. - Fracture Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES

32.5 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

234.9 ft. - Fracture Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

333 ft. - Fracture Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES