Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 16, 2020, 06:59 AM
  • F 0025_F 0024_07162020_002141.mp4

Date
07/15/2020
W/O
838889
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00033
PipeID
P10115
Time
11:59 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7921
Sewer Name
JOINT OUTFALL F - UNIT 1
City
long beach
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_838889_TV03167_JUL2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
69 in.
Width
12 in.
Upstream MH
F 0025
Downstream MH
F 0024
Dir. of Survey
Downstream
Length Surveyed
480 ft.
Total Length
480 ft.
Structural Index
4
Structural Quick
5e3R
Structural Rating
1433
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
1433
Pipe schematic from manhole F 0025 to F 0024
MH: F 0025MH: F 0024downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 00252 ft. MGO - General Observation - 40% MAG COAT2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start477 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish477 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish480 ft. AMH - Downstream Manhole, Survey Ends - F 0024480 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish480 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
2.1SAP
0MWL
480AMHF 0024
480SAP
477SSS
0MWM
477SRC
2.2SRV
2MGO40% MAG COAT
480SRV
0AMHF 0025
2SRC
2SSS

Properties (7)

additional_info
SC411780
custom_field_three
AGGREGATE PROJECTING/ REINFORCEMENT CORRODED
custom_field_two
2
customer
1
datetime
2020-07-15T23:59:08-07:00
documentation
PROPIPE
is_lateral_inspection
false