Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 9, 2020, 09:14 AM
  • 08 0270_08 0269 _07092020_023008.mp4

Date
07/09/2020
W/O
838895
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00004
PipeID
P00312
Time
2:14 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7909
Sewer Name
DEL AMO TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_838895_TV08167_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
08 0270
Downstream MH
08 0269
Dir. of Survey
Downstream
Length Surveyed
348.7 ft.
Total Length
348.7 ft.
Structural Index
3
Structural Quick
4332
Structural Rating
19
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
22
Pipe schematic from manhole 08 0270 to 08 0269
MH: 08 0270MH: 08 0269downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 02700 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start60.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start60.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish114.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"117.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"229.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"232.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"233.7 ft. FM - Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES245.6 ft. IS - Infiltration Stain, from 07 to 09 o'clock, within 8 inches of joint: YES317.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"319.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"324.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES333.8 ft. JOM - Joint Offset Medium341.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish341.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES341.6 ft. ID - Infiltration Dripper, from 10 to 12 o'clock, within 8 inches of joint: YES348.7 ft. AMH - Downstream Manhole, Survey Ends - 08 0269348.7 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (8)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    60.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

    233.7 ft. - Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, from 07 to 09 o'clock, within 8 inches of joint: YES

    245.6 ft. - Infiltration Stain, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    324.7 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Joint Offset Medium

    333.8 ft. - Joint Offset Medium

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    341.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, from 10 to 12 o'clock, within 8 inches of joint: YES

    341.6 ft. - Infiltration Dripper, from 10 to 12 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
348.7AMH08 0269
317.1TFC
0AMH08 0270
229.7TFC
0MWM
0MWL
341.6CM
60.4CM
245.6IS
114.9TFC
60.4FM
341.6FM
341.6ID
333.8JOM
117.1TFC
232.4TFC
348.7MGOCONNECTION AT MH 3 O'CLOCK
319.5TFC
2.3FM
324.7FL
233.7FM

Properties (7)

additional_info
SC41168
custom_field_three
MULTIPLE FRACTURE'S/ CRACKS
custom_field_two
2
customer
1
datetime
2020-07-09T02:14:50-07:00
documentation
PROPIPE
is_lateral_inspection
false