Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 9, 2020, 07:16 AM
  • 05 1797_05 1796 _07092020_003940.mp4

Date
07/09/2020
W/O
838734
Weather
Dry
Operator/Surveyor
N.zahreddine
Sewer ID
Z00466
PipeID
P07019
Time
12:16 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7323
Sewer Name
JANET LANE TRUNK
City
Torrance
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
31
Purpose
Routine Assessment
Project
RFIR_WO_838734_TV05303_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
24 in.
Upstream MH
05 1797
Downstream MH
05 1796
Dir. of Survey
Downstream
Length Surveyed
340.4 ft.
Total Length
340.4 ft.
Structural Index
4
Structural Quick
4531
Structural Rating
23
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
23
Pipe schematic from manhole 05 1797 to 05 1796
MH: 05 1797MH: 05 1796downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 17970 ft. MWL - Water Level, 25 %of cross sectional area46.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES130.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES187.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"191.3 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES196.5 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES199.9 ft. RPP - Repair Patch, from 09 to 03 o'clock, within 8 inches of joint: YES - metal236.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES311.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES340.4 ft. AMH - Downstream Manhole, Survey Ends - 05 1796

Observation photos (7)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    46.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    130.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    191.3 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    196.5 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Repair Patch, from 09 to 03 o'clock, within 8 inches of joint: YES - metal

    199.9 ft. - Repair Patch, from 09 to 03 o'clock, within 8 inches of joint: YES - metal

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    236.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    311.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
236.2FM
191.3FM
130.7FM
0MWM
187.4TB
340.4AMH05 1796
0AMH05 1797
311.4FM
46.1CM
196.5FM
199.9RPPmetal
0MWL

Properties (7)

additional_info
SC411315
custom_field_three
multiple fracture
custom_field_two
3
customer
1
datetime
2020-07-09T00:16:17-07:00
documentation
Pro pipe
is_lateral_inspection
false