Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 19, 2020, 04:24 AM
  • 15 0673_15 0672_06182020_213700.mp4

Date
06/18/2020
W/O
833720
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00602
PipeID
P12565
Time
9:24 PM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7853
Sewer Name
EL MONTE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_833720_TV15208_JUN2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0673
Downstream MH
15 0672
Dir. of Survey
Downstream
Length Surveyed
273.1 ft.
Total Length
273.1 ft.
Structural Index
3
Structural Quick
3J2J
Structural Rating
268
O&M Index
2
O&M Quick
412J
O&M Rating
112
Overall Index
2
Overall Quick
Overall Rating
380
Pipe schematic from manhole 15 0673 to 15 0672
MH: 15 0673MH: 15 0672downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 06732 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start6.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start171.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"225.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"271.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish271.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish271.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish271.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE273.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK273.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0672

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    6.8 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    271.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (16)

DistanceCodeObservation
2DAGS
0MGOCONNECTION AT MH 9 O'CLOCK
225.8TFC
271.4SSS
273.1MGOCONNECTION AT MH 3 O'CLOCK
2SAP
271.4SAP
171.3TFC
0MGOCOCKROACHES IN MANHOLE
271.4DAGS
0MWL
0MWM
6.8SSS
273.1AMH15 0672
0AMH15 0673
271.4MGOCOCKROACHES IN MANHOLE

Properties (7)

additional_info
SC411294
custom_field_three
SPALLING/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2020-06-18T21:24:46-07:00
documentation
PRO PIPE
is_lateral_inspection
false