Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 2, 2020, 09:14 AM
  • 18 0002_18 0001 _07022020_023111.mp4

Date
07/02/2020
W/O
833710
Weather
Dry
Operator/Surveyor
EN. RUIZ
Sewer ID
Z00713
PipeID
P13817
Time
2:14 AM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7773
Sewer Name
18 WALNUT WAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_833710_TV18059_JUN2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0002
Downstream MH
18 0001
Dir. of Survey
Downstream
Length Surveyed
353.8 ft.
Total Length
353.8 ft.
Structural Index
3
Structural Quick
3M2M
Structural Rating
350
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
490
Pipe schematic from manhole 18 0002 to 18 0001
MH: 18 0002MH: 18 0001downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 00020 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - 60% MAG COAT2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start19.7 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 4", 6"50.4 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6" - OPEN90 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6" - OPEN108.4 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6" - OPEN117.6 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6" - OPEN148.1 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6" - OPEN203.8 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6" - OPEN227.6 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6" - OPEN252 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6" - OPEN295.3 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6" - OPEN331.9 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6" - OPEN344.4 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: YES, 4", 6"349.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish351 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish351.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish353.8 ft. MGO - General Observation - ROACHES @ MH353.8 ft. AMH - Downstream Manhole, Survey Ends - 18 0001

Observation photos (4)

  • General Observation - ROACHES @ MH

    0 ft. - General Observation - ROACHES @ MH

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • General Observation - ROACHES @ MH

    353.8 ft. - General Observation - ROACHES @ MH

Observations (25)

DistanceCodeObservation
351DAGS
0AMH18 0002
50.4TFOPEN
0MWL
351.4SAP
90TFOPEN
295.3TFOPEN
252TFOPEN
2SSS
2.1MGO60% MAG COAT
2DAGS
331.9TFOPEN
108.4TFOPEN
19.7TFA
349.9SSS
0MGOROACHES @ MH
344.4TFA
353.8MGOROACHES @ MH
353.8AMH18 0001
2.1SAP
148.1TFOPEN
117.6TFOPEN
203.8TFOPEN
0MWM
227.6TFOPEN

Properties (7)

additional_info
SC427458
custom_field_three
AGGREGATE, SPALLING
custom_field_two
2
customer
1
datetime
2020-07-02T02:14:53-07:00
documentation
PRO PIPE
is_lateral_inspection
false