Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 26, 2020, 07:07 AM
  • 05 0386_05 0385_06262020_004526.mp4

Date
06/26/2020
W/O
833501
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00432
PipeID
P05598
Time
12:07 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7747
Sewer Name
DISTRICT #5 MAIN RELIEF TRUNK
City
HAWTHORNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_833501_TV05179_JUN2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
05 0386
Downstream MH
05 0385
Dir. of Survey
Downstream
Length Surveyed
400.2 ft.
Total Length
400.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 05 0386 to 05 0385
MH: 05 0386MH: 05 0385downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 03860 ft. MWM - Water Mark, 75 %of cross sectional area2.1 ft. MGO - General Observation - MAG COAT2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"400 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish400.2 ft. AMH - Downstream Manhole, Survey Ends - 05 0385

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MWL
0AMH05 0386
2.1MGOMAG COAT
0MWM
3.6TF
400.2AMH05 0385
400SAV
2.1SAV

Properties (7)

additional_info
SC411756
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2020-06-26T00:07:08-07:00
documentation
PROPIPE
is_lateral_inspection
false