Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 26, 2020, 09:35 AM
  • 05 0368_05 0367_06262020_025919.mp4

Date
06/26/2020
W/O
833501
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00432
PipeID
P05584
Time
2:35 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7747
Sewer Name
DISTRICT #5 MAIN RELIEF TRUNK
City
HAWTHORNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_833501_TV05179_JUN2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
33 in.
Upstream MH
05 0368
Downstream MH
05 0367
Dir. of Survey
Downstream
Length Surveyed
330.8 ft.
Total Length
330.8 ft.
Structural Index
4
Structural Quick
5432
Structural Rating
26
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
31
Pipe schematic from manhole 05 0368 to 05 0367
MH: 05 0368MH: 05 0367downstream0 ft. MWM - Water Mark, 75 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 03682.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. MGO - General Observation - MAG COAT63.8 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO70.6 ft. SRV - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: NO72.9 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start73.4 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES119.9 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Finish284.6 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO330.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish330.8 ft. AMH - Downstream Manhole, Survey Ends - 05 0367

Observation photos (6)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO

    63.8 ft. - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: NO

    70.6 ft. - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start

    72.9 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES

    73.4 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

    284.6 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

Observations (13)

DistanceCodeObservation
330.8SAV
73.4SAP
0MWM
70.6SRV
72.9SRV
0MWL
119.9SRV
2.5SAV
0AMH05 0368
63.8SRV
284.6SRV
2.5MGOMAG COAT
330.8AMH05 0367

Properties (7)

additional_info
SC411756
custom_field_three
AGGREGATE VISIBLE/ REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2020-06-26T02:35:54-07:00
documentation
PROPIPE
is_lateral_inspection
false