- Date
- 06/02/2020
- W/O
- 834129
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00093
- PipeID
- P08962
- Time
- 1:49 AM
- Certificate
- U-111-11880
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K7681
- Sewer Name
- JOINT OUTFALL B - UNIT 5C
- City
- PASADENA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 16
- Page No.
- 11
- Purpose
- Routine Assessment
- Project
- RFIR_WO_834129_TV16034_JUN2020
- Sewer Type
- Gravity
- Material
- NRCP
- Shape
- Circular
- Height
- 21 in.
- Width
- 63 in.
- Upstream MH
- B 0450
- Downstream MH
- B 0449
- Dir. of Survey
- Downstream
- Length Surveyed
- 233.2 ft.
- Total Length
- 233.2 ft.
- Structural Index
- 3
- Structural Quick
- 3H2H
- Structural Rating
- 230
- O&M Index
- 2
- O&M Quick
- 2H00
- O&M Rating
- 92
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 322
Pipe schematic from manhole B 0450 to B 0449 Observation photos (4)

2 ft. - General Observation - 85% MAG COAT

2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

231.2 ft. - General Observation - ROACHES @ MANHOLE