Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 2, 2020, 05:02 AM
  • B 0438_B 0437_06012020_221942.mp4

Date
06/01/2020
W/O
834129
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00093
PipeID
P08950
Time
10:02 PM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7681
Sewer Name
JOINT OUTFALL B - UNIT 5C
City
PASADENA
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_834129_TV16034_JUN2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
57 in.
Upstream MH
B 0438
Downstream MH
B 0437
Dir. of Survey
Downstream
Length Surveyed
388.2 ft.
Total Length
388.2 ft.
Structural Index
3
Structural Quick
3N2N
Structural Rating
380
O&M Index
2
O&M Quick
2N00
O&M Rating
154
Overall Index
2
Overall Quick
Overall Rating
534
Pipe schematic from manhole B 0438 to B 0437
MH: B 0438MH: B 0437downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 04380 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. MGO - General Observation - ROACHES @ MANHOLE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.7 ft. MGO - General Observation - 65% MAG COAT4.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start387.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish387.1 ft. MGO - General Observation - ROACHES @ MANHOLE387.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish387.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish388 ft. MGO - General Observation - ROACHES @ MH388.2 ft. AMH - Downstream Manhole, Survey Ends - B 0437388.2 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE

Observation photos (6)

  • General Observation - ROACHES @ MANHOLE

    0 ft. - General Observation - ROACHES @ MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - 65% MAG COAT

    4.7 ft. - General Observation - 65% MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.7 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ROACHES @ MANHOLE

    387.1 ft. - General Observation - ROACHES @ MANHOLE

Observations (16)

DistanceCodeObservation
388.2AMHB 0437
4.7MGO65% MAG COAT
387.1SAP
4.6SAP
2DAGS
4.7SSS
387.1MGOROACHES @ MANHOLE
387.1DAGS
0MWM
388MGOROACHES @ MH
0AMHB 0438
0MWL
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
387.1SSS
0MGOROACHES @ MANHOLE
388.2MGOCONN @ MH 3 O'CLOCK/ACTIVE

Properties (7)

additional_info
SC411273
custom_field_three
SPALLING/PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2020-06-01T22:02:38-07:00
documentation
PRO PIPE
is_lateral_inspection
false