Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 12, 2020, 08:31 AM
  • 19 0296_19 0295_06122020_013446.mp4

Date
06/12/2020
W/O
833771
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00718
PipeID
P15188
Time
1:31 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7729
Sewer Name
ARTESIA-CERRITOS TRUNK
City
ARTESIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_833771_TV19059_JUN2020
Sewer Type
Siphon
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
19 0295
Downstream MH
19 0296
Dir. of Survey
Upstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 19 0295 to 19 0296
MH: 19 0295MH: 19 0296upstream0 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES0 ft. MSA - Survey Abandoned - VIEW OF U/S SIPHON FROM D/S MH0 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES0 ft. LU - Alignment Up, 45 %2.1 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/UNKNOWN2.1 ft. MWL - Water Level, 100 %of cross sectional area2.1 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/UNKNOWN2.1 ft. MWM - Water Mark, 100 %of cross sectional area2.1 ft. MGO - General Observation - ROACHES @ MH2.1 ft. AMH - Downstream Manhole, Survey Begins - 19 0295 SE

Observation photos (3)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    2.1 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Survey Abandoned - VIEW OF U/S SIPHON FROM D/S MH

    2.1 ft. - Survey Abandoned - VIEW OF U/S SIPHON FROM D/S MH

  • Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    2.1 ft. - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
0MGOCONN @ MH 3 O'CLOCK/UNKNOWN
2.1DAE
2.1MSAVIEW OF U/S SIPHON FROM D/S MH
0MWL
0MGOCONN @ MH 9 O'CLOCK/UNKNOWN
0MWM
0MGOROACHES @ MH
2.1CM
0AMH19 0295 SE
2.1LU

Properties (7)

additional_info
SC411387
custom_field_three
RFIR NO SEVERE DEFECTS
custom_field_two
5
customer
1
datetime
2020-06-12T01:31:00-07:00
documentation
PROPIPE
is_lateral_inspection
false