Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 8, 2020, 08:02 AM
  • 05 1284_05 1283_06082020_011818.mp4

Date
06/08/2020
W/O
833683
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00518
PipeID
P06498
Time
1:02 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7718
Sewer Name
SO HAWTHORNE-WARFIELD AV EXT TR, SECT 4
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_833683_TV05332_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
12 in.
Upstream MH
05 1284
Downstream MH
05 1283
Dir. of Survey
Downstream
Length Surveyed
322.3 ft.
Total Length
322.3 ft.
Structural Index
3
Structural Quick
423L
Structural Rating
334
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
338
Pipe schematic from manhole 05 1284 to 05 1283
MH: 05 1284MH: 05 1283downstream0 ft. MGO - General Observation - ROACHES @ MH0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 05 12840 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.2 ft. FM - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES7 ft. FM - Fracture Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES13.4 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES58.9 ft. CM - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES124.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES190.1 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - SEPARATED/BROKEN CONN/ACTIVE320 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish322 ft. MGO - General Observation - ROACHES @ MH322 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish322.3 ft. AMH - Downstream Manhole, Survey Ends - 05 1283322.3 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE322.3 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE

Observation photos (6)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

    6.2 ft. - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

  • Deposits Settled Other,  10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES

    13.4 ft. - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES

  • Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

    58.9 ft. - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    124.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - SEPARATED/BROKEN CONN/ACTIVE

    190.1 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - SEPARATED/BROKEN CONN/ACTIVE

Observations (20)

DistanceCodeObservation
2CM
7FM
0MGOROACHES @ MH
320SSS
124.5CM
13.4DSZ
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
0AMH05 1284
322.3AMH05 1283
6.2FM
322.3MGOCONN @ MH 9 O'CLOCK/ACTIVE
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
58.9CM
0MWM
322MGOROACHES @ MH
0MWL
322CM
322.3MGOCONN @ MH 3 O'CLOCK/ACTIVE
2SSS
190.1TFDSEPARATED/BROKEN CONN/ACTIVE

Properties (7)

additional_info
SC411375
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-06-08T01:02:51-07:00
documentation
PRO PIPE
is_lateral_inspection
false