- Date
- 06/04/2020
- W/O
- 833683
- Weather
- Dry
- Operator/Surveyor
- N.ZAHREDDINE
- Sewer ID
- Z00518
- PipeID
- P06464
- Time
- 1:54 AM
- Certificate
- U-109-7948
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K7321
- Sewer Name
- SO HAWTHORNE-WARFIELD AV EXT TR, SECT 4
- City
- REDONDO BEACH
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 16
- Purpose
- Routine Assessment
- Project
- RFIR_WO_833683_TV05332_JUN2020
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 18 in.
- Width
- 24 in.
- Upstream MH
- 05 1256
- Downstream MH
- 05 1255
- Dir. of Survey
- Downstream
- Length Surveyed
- 398.8 ft.
- Total Length
- 398.8 ft.
- Structural Index
- 3
- Structural Quick
- 4N3O
- Structural Rating
- 691
- O&M Index
- 2
- O&M Quick
- 2J00
- O&M Rating
- 106
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 797
Pipe schematic from manhole 05 1256 to 05 1255 Observation photos (4)

17.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

31.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

48.9 ft. - Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 2", 6" - ACTIVE

131.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start