Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 2, 2020, 10:00 AM
  • A 0814_A 0813_07022020_032222.mp4

Date
07/02/2020
W/O
833719
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00325
PipeID
P08314
Time
3:00 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7814
Sewer Name
JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_833719_TV15209_JUN2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
24 in.
Upstream MH
A 0814
Downstream MH
A 0813
Dir. of Survey
Downstream
Length Surveyed
143.3 ft.
Total Length
143.3 ft.
Structural Index
3
Structural Quick
3D2C
Structural Rating
118
O&M Index
2
O&M Quick
4125
O&M Rating
14
Overall Index
3
Overall Quick
Overall Rating
132
Pipe schematic from manhole A 0814 to A 0813
MH: A 0814MH: A 0813downstream0 ft. MWM - Water Mark, 70 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 081412.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.4 ft. MGO - General Observation - MAG COATING ATTATCHED18.5 ft. LL - Alignment Left, 15 %, Start44 ft. LL - Alignment Left, 15 %, Finish45.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start143.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish143.3 ft. AMH - Downstream Manhole, Survey Ends - A 0813143.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    12.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    45.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
143.3SSS
143.3AMHA 0813
12.4SAP
12.4MGOMAG COATING ATTATCHED
0MWM
0MWL
18.5LL
45.2SSS
0AMHA 0814
44LL
143.3SAP

Properties (8)

additional_info
SC411624
custom_field_three
AGGREGATE PROJECTING, SPALLING
custom_field_two
3
customer
1
datetime
2020-07-02T03:00:11-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
29427