Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 19, 2020, 07:44 AM
  • 15 0281_15 0280_06192020_005707.mp4

Date
06/19/2020
W/O
833717
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00591
PipeID
P12204
Time
12:44 AM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7856
Sewer Name
AMAR ROAD TRUNK
City
LA PUENTE
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_833717_TV15142_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
15 0281
Downstream MH
15 0280
Dir. of Survey
Downstream
Length Surveyed
352.4 ft.
Total Length
352.4 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
412[
O&M Rating
284
Overall Index
2
Overall Quick
Overall Rating
290
Pipe schematic from manhole 15 0281 to 15 0280
MH: 15 0281MH: 15 0280downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 02810 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start - MINERAL DEPOSITS78 ft. FS - Fracture Spiral, from 01 to 04 o'clock, within 8 inches of joint: YES - WITH POSSIBLE SOIL99.4 ft. FS - Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES178.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"223.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"277.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"343.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"350.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish350.3 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish352 ft. MGO - General Observation - CONNECTION @ 9 O'CLOCK - D/S MH - POSSIBLY CAPPED352.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE352.4 ft. AMH - Downstream Manhole, Survey Ends - 15 0280

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Other, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start - MINERAL DEPOSITS

    2 ft. - Deposits Attached Other, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start - MINERAL DEPOSITS

  • Fracture Spiral, from 01 to 04 o'clock, within 8 inches of joint: YES - WITH POSSIBLE SOIL

    78 ft. - Fracture Spiral, from 01 to 04 o'clock, within 8 inches of joint: YES - WITH POSSIBLE SOIL

  • Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

    99.4 ft. - Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    352.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (16)

DistanceCodeObservation
352MGOCONNECTION @ 9 O'CLOCK - D/S MH - POSSIBLY CAPPED
178.4TFC
0AMH15 0281
352.4MGOCOCKROACHES IN MANHOLE
0MWM
2DAGS
350.3DAGS
277.7TFC
223.5TFC
352.4AMH15 0280
78FSWITH POSSIBLE SOIL
350.3DAZ
343.6TFC
99.4FS
2DAZMINERAL DEPOSITS
0MWL

Properties (7)

additional_info
SC411297
custom_field_three
SPIRAL FRACTURES
custom_field_two
2
customer
1
datetime
2020-06-19T00:44:29-07:00
documentation
PRO PIPE
is_lateral_inspection
false