Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 22, 2020, 10:15 AM
  • 02 0032A_02 0032_06222020_032948.mp4

Date
06/22/2020
W/O
833685
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00234
PipeID
P03064
Time
3:15 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7736
Sewer Name
ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Routine Assessment
Project
RFIR_WO_833685_TV02341_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
8 in.
Upstream MH
02 0032
Downstream MH
02 0032A
Dir. of Survey
Upstream
Length Surveyed
180.9 ft.
Total Length
180.9 ft.
Structural Index
3
Structural Quick
3F2F
Structural Rating
175
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
175
Pipe schematic from manhole 02 0032 to 02 0032A
MH: 02 0032MH: 02 0032Aupstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/OPEN0 ft. AMH - Upstream Manhole, Survey Ends - 02 0032A0 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish2.9 ft. MGO - General Observation - ROACHES @ MH2.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish34.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"93.9 ft. MWL - Water Level, 20 %of cross sectional area177 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start178.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start180.9 ft. MWL - Water Level, 10 %of cross sectional area180.9 ft. MWM - Water Mark, 15 %of cross sectional area180.9 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/UNKNOWN180.9 ft. AMH - Downstream Manhole, Survey Begins - 02 0032

Observation photos (1)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
2SSS
0MWL
3.9CM
146.2TFC
178MGOROACHES @ MH
0MWM
180.9MGOCONN @ MH 9 O'CLOCK/OPEN
0MGOCONN @ MH 3 O'CLOCK/UNKNOWN
178SSS
87MWL
180.9AMH02 0032A
180.9CM
0AMH02 0032

Properties (5)

additional_info
SC411395
customer
1
datetime
2020-06-22T03:15:23-07:00
documentation
PROPIPE
is_lateral_inspection
false