Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 22, 2020, 10:52 AM
  • 02 0031_02 0030_06222020_040150.mp4

Date
06/22/2020
W/O
833685
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00234
PipeID
P03062
Time
3:52 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7736
Sewer Name
ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Routine Assessment
Project
RFIR_WO_833685_TV02341_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
10 in.
Upstream MH
02 0031
Downstream MH
02 0030
Dir. of Survey
Downstream
Length Surveyed
236.8 ft.
Total Length
236.8 ft.
Structural Index
3
Structural Quick
3H2H
Structural Rating
233
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
233
Pipe schematic from manhole 02 0031 to 02 0030
MH: 02 0031MH: 02 0030downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 00312 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start65 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"82.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN165.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"168.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"230.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"234 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish236 ft. MGO - General Observation - ROACHES @ MH236.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish236.8 ft. AMH - Downstream Manhole, Survey Ends - 02 0030

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
168.3TFC
165.9TFC
236.8CM
82.6TFOPEN
230.8TFC
2SSS
236.8AMH02 0030
234SSS
0MWM
236MGOROACHES @ MH
2CM
0MWL
65TFC
0AMH02 0031

Properties (7)

additional_info
SC411395
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-06-22T03:52:39-07:00
documentation
PROPIPE
is_lateral_inspection
false