Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 19, 2020, 10:00 AM
  • 02 0009_02 0008_06192020_031732.mp4

Date
06/19/2020
W/O
833685
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00234
PipeID
P03035
Time
3:00 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7735
Sewer Name
ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_833685_TV02341_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
15 in.
Upstream MH
02 0009
Downstream MH
02 0008
Dir. of Survey
Downstream
Length Surveyed
367.3 ft.
Total Length
367.3 ft.
Structural Index
3
Structural Quick
4C3L
Structural Rating
424
O&M Index
2
O&M Quick
2212
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
430
Pipe schematic from manhole 02 0009 to 02 0008
MH: 02 0009MH: 02 0008downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 02 00090 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start34.6 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES65.2 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES74.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start114.5 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"122.3 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES132 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start184 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"254.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES257 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"259.1 ft. RFB - Roots Fine Barrell, from 10 to 02 o'clock259.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish259.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish259.1 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start315.1 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"315.2 ft. RFC - Roots Fine Connection, at 12 o'clock332.1 ft. RFJ - Roots Fine Joint, at 02 o'clock, within 8 inches of joint: YES362 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish365 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish367.3 ft. AMH - Downstream Manhole, Survey Ends - 02 0008

Observation photos (9)

  • Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    34.6 ft. - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    65.2 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    74.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    122.3 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    132 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    257 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Roots Fine Barrell, from 10 to 02 o'clock

    259.1 ft. - Roots Fine Barrell, from 10 to 02 o'clock

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    259.1 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 02 o'clock, within 8 inches of joint: YES

    332.1 ft. - Roots Fine Joint, at 02 o'clock, within 8 inches of joint: YES

Observations (25)

DistanceCodeObservation
2SSS
259.1RFB
184TB
259.1FL
332.1RFJ
315.1TBA
367.3AMH02 0008
259.1CM
259.1FM
0MWM
114.5TB
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
65.2CL
362FM
0AMH02 0009
315.2RFC
0MWL
254.6DAGS
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
132FL
74.1CM
257TB
365SSS
122.3FL
34.6CM

Properties (7)

additional_info
SC411394
custom_field_three
MULTIPLE FRACTURE'S/ CRACKS
custom_field_two
2
customer
1
datetime
2020-06-19T03:00:55-07:00
documentation
PROPIPE
is_lateral_inspection
false