Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 22, 2020, 08:41 AM
  • 02 0008_02 0007 _06222020_015540.mp4

Date
06/22/2020
W/O
833685
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00234
PipeID
P03034
Time
1:41 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7736
Sewer Name
ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_833685_TV02341_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
15 in.
Upstream MH
02 0007
Downstream MH
02 0008
Dir. of Survey
Upstream
Length Surveyed
372.9 ft.
Total Length
372.9 ft.
Structural Index
3
Structural Quick
4C3D
Structural Rating
300
O&M Index
1
O&M Quick
2213
O&M Rating
7
Overall Index
2
Overall Quick
Overall Rating
307
Pipe schematic from manhole 02 0007 to 02 0008
MH: 02 0007MH: 02 0008upstream0 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 02 00082.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish19.6 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"19.6 ft. RFC - Roots Fine Connection, at 12 o'clock91.1 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start91.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish93.4 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES94.9 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"95.8 ft. RFB - Roots Fine Barrell, at 12 o'clock95.9 ft. RFJ - Roots Fine Joint, from 11 to 03 o'clock, within 8 inches of joint: YESR - 5% ROOTS149 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"212.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"223 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start267.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"269.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES295.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES330.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN350 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN370.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start372.9 ft. MWL - Water Level, 20 %of cross sectional area372.9 ft. MWM - Water Mark, 25 %of cross sectional area372.9 ft. AMH - Downstream Manhole, Survey Begins - 02 0007

Observation photos (8)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    77.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 10 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES

    103.8 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    149.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    223.9 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Roots Fine Barrell, at 12 o'clock

    277.1 ft. - Roots Fine Barrell, at 12 o'clock

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    278 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

    279.5 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    281.8 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
278TBA
105.4TFA
22.9TFOPEN
103.8DAGS
42.4TFOPEN
160.8TFA
0MWL
353.3TBA
2SSS
370SSS
277RFJ5% ROOTS
223.9TBA
281.8FM
372.9FM
0MWM
281.8CM
277.1RFB
372.9AMH02 0008
353.3RFC
149.9CM
279.5RFJ
0AMH02 0007
77.1CL

Properties (7)

additional_info
SC411395
custom_field_three
MULTIPLE FRACTURE'S/ CRACKS
custom_field_two
2
customer
1
datetime
2020-06-22T01:41:17-07:00
documentation
PROPIPE
is_lateral_inspection
false