Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 8, 2020, 09:51 AM
  • 05 1485_05 1484_06082020_030507.mp4

Date
06/08/2020
W/O
833689
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00438
PipeID
P06711
Time
2:51 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7719
Sewer Name
EL NIDO TRUNK
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_833689_TV05300_JUN2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
24 in.
Upstream MH
05 1484
Downstream MH
05 1485
Dir. of Survey
Upstream
Length Surveyed
281.9 ft.
Total Length
281.9 ft.
Structural Index
3
Structural Quick
3K2H
Structural Rating
274
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
274
Pipe schematic from manhole 05 1484 to 05 1485
MH: 05 1484MH: 05 1485upstream0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 05 14850 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish43.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN68.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN98.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN153.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN163.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN211.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN259.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish278 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start279.9 ft. MGO - General Observation - 70% MAG COAT279.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start279.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start281.9 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE281.9 ft. MWM - Water Mark, 25 %of cross sectional area281.9 ft. MGO - General Observation - ROACHES @ MH281.9 ft. MWL - Water Level, 20 %of cross sectional area281.9 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/UNKNOWN281.9 ft. AMH - Downstream Manhole, Survey Begins - 05 1484

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
213.4TFOPEN
238.3TFOPEN
2MGO70% MAG COAT
2SSS
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
183.5TFOPEN
0MWM
281.9SSS
281.9AMH05 1485
0MGOROACHES @ MH
128.5TFOPEN
70.5TFOPEN
0MWL
2SAP
118.5TFOPEN
0MGOCONN @ MH 9 O'CLOCK/UNKNOWN
281.9SAP
3.9SAV
0AMH05 1484
22.3SAV

Properties (7)

additional_info
SC411376
custom_field_three
AGGREGATE PROJECTING/ SURFACE SPALLING
custom_field_two
2
customer
1
datetime
2020-06-08T02:51:10-07:00
documentation
PROPIPE
is_lateral_inspection
false