Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 8, 2020, 11:21 AM
  • 05 1483_05 1482_06082020_043013.mp4

Date
06/08/2020
W/O
833689
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00438
PipeID
P06708
Time
4:21 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7719
Sewer Name
EL NIDO TRUNK
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_833689_TV05300_JUN2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
21 in.
Upstream MH
05 1483
Downstream MH
05 1482
Dir. of Survey
Downstream
Length Surveyed
286.3 ft.
Total Length
286.3 ft.
Structural Index
3
Structural Quick
3J2J
Structural Rating
285
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
285
Pipe schematic from manhole 05 1483 to 05 1482
MH: 05 1483MH: 05 1482downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 14830 ft. MWM - Water Mark, 10 %of cross sectional area2 ft. MGO - General Observation - 60% MAG COAT2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start64.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"150.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"231.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"286 ft. MGO - General Observation - ROACHES @ MH286.3 ft. AMH - Downstream Manhole, Survey Ends - 05 1482286.3 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/CAPPED286.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish286.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
231.6TF
2MGO60% MAG COAT
150.1TFC
286.3AMH05 1482
0MWL
286.3MGOCONN @ MH 3 O'CLOCK/CAPPED
64.7TFC
286MGOROACHES @ MH
286.3SAP
0AMH05 1483
286.3SSS
2.1SSS
2.1SAP
0MWM

Properties (7)

additional_info
SC411376
custom_field_three
AGGREGATE PROJECTING/ SURFACE SPALLING
custom_field_two
2
customer
1
datetime
2020-06-08T04:21:10-07:00
documentation
PROPIPE
is_lateral_inspection
false