Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 9, 2020, 08:17 AM
  • 05 1481_05 1480_06092020_013141.mp4

Date
06/09/2020
W/O
833689
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00438
PipeID
P06705
Time
1:17 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7721
Sewer Name
EL NIDO TRUNK
City
REDONDO BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_833689_TV05300_JUN2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
27 in.
Upstream MH
05 1480
Downstream MH
05 1481
Dir. of Survey
Upstream
Length Surveyed
367.9 ft.
Total Length
367.9 ft.
Structural Index
3
Structural Quick
3N2N
Structural Rating
368
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
368
Pipe schematic from manhole 05 1480 to 05 1481
MH: 05 1480MH: 05 1481upstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 05 14810 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/CAPPED139.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN204.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"286.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN352.9 ft. CM - Crack Multiple, from 12 to 01 o'clock, within 8 inches of joint: YES365.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start365.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start365.9 ft. MGO - General Observation - 65% MAG COAT367.9 ft. AMH - Downstream Manhole, Survey Begins - 05 1480367.9 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED367.9 ft. MWM - Water Mark, 15 %of cross sectional area367.9 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 12 to 01 o'clock, within 8 inches of joint: YES

    15 ft. - Crack Multiple, from 12 to 01 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
0AMH05 1480
367.9MGOCONN @ MH 9 O'CLOCK/CAPPED
367.9SSS
15CM
228.1TFOPEN
2.5SAP
367.9SAP
0MGOCONN @ MH 9 O'CLOCK/CAPPED
163TFC
0MWM
367.9AMH05 1481
0MWL
2.5SSS
81.6TFOPEN
367.9MGOCONN @ MH 3 O'CLOCK/CAPPED
2MGO65% MAG COAT

Properties (7)

additional_info
SC411379
custom_field_three
AGGREGATE PROJECTING/ SURFACE SPALLING
custom_field_two
2
customer
1
datetime
2020-06-09T01:17:36-07:00
documentation
PROPIPE
is_lateral_inspection
false