Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 30, 2015, 10:45 AM
  • 14 0890_14 0889_30122015_024529.mp4

Date
12/30/2015
W/O
541692
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00579
PipeID
P22365
Time
2:45 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3062
Sewer Name
14 TRUNK "C"
City
PALMDALE
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
13
Purpose
Routine Assessment
Project
WO_541692_TV14020_DEC2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
14 0890
Downstream MH
14 0889
Dir. of Survey
Downstream
Length Surveyed
354.5 ft.
Total Length
354.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
140
Pipe schematic from manhole 14 0890 to 14 0889
MH: 14 0890MH: 14 0889downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 08902 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start352.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish354.5 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK354.5 ft. AMH - Downstream Manhole, Survey Ends - 14 0889

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
352.8DAGS
0MWM
354.5MGOCONNECTION AT MH 3 O'CLOCK
354.5AMH14 0889
0MWL
0AMH14 0890
2DAGS

Properties (6)

additional_info
SC224847
custom_field_two
4
customer
LACSD
datetime
2015-12-30T02:45:15-08:00
documentation
PRO PIPE
is_lateral_inspection
false