Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 4, 2015, 08:19 AM
  • 22 0751_22 0750_20151214_105445.mp4

Date
12/04/2015
W/O
536652
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00821
PipeID
P17108
Time
12:19 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2878
Sewer Name
22 PUDDINGSTONE TRUNK, SECTS 1&2
City
SAN DIMAS, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
23
Purpose
Routine Assessment
Project
WO_536652_TV22057_NOV2015
Sewer Type
SIPHON
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0751
Downstream MH
22 0750
Dir. of Survey
Downstream
Length Surveyed
92.5 ft.
Total Length
92.5 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 22 0751 to 22 0750
MH: 22 0751MH: 22 0750downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 07512 ft. MGO - General Observation - MAGNESIUM H.O. START 80%2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start47.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"92 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish92.5 ft. MSA - Survey Abandoned - DUE CAMERA ISSUES

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
2MGOMAGNESIUM H.O. START 80%
0MWL
92SAV
92.5MSADUE CAMERA ISSUES
47.6TFC
0MWM
0AMH22 0751
2SAV

Properties (6)

additional_info
SC205646
custom_field_two
5
customer
LACSD
datetime
2015-12-04T00:19:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false