Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 3, 2015, 08:00 AM
  • 22 0752_22 0751_20151204_001522.mp4

Date
12/03/2015
W/O
536652
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00821
PipeID
P17109
Time
12:00 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2878
Sewer Name
22 PUDDINGSTONE TRUNK, SECTS 1&2
City
SAN DIMAS, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
23
Purpose
Routine Assessment
Project
WO_536652_TV22057_NOV2015
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0752
Downstream MH
22 0751
Dir. of Survey
Downstream
Length Surveyed
351.1 ft.
Total Length
351.1 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
207
O&M Index
2
O&M Quick
2M00
O&M Rating
138
Overall Index
3
Overall Quick
Overall Rating
345
Pipe schematic from manhole 22 0752 to 22 0751
MH: 22 0752MH: 22 0751downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 07520 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAGNESIUM H.O. START 80%2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"49.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"101.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"150 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"202.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"254.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"302.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"302.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"346.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"348 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish348.2 ft. MGO - General Observation - MAGNESIUM H.O. FINISH348.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish351.1 ft. AMH - Downstream Manhole, Survey Ends - 22 0751351.1 ft. MGO - General Observation - INFILTRATION AT MANHOLE

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
49.9TFC
202.2TFC
302.3TFC
0MWL
0AMH22 0752
101.5TFC
302.3TFC
348.2MGOMAGNESIUM H.O. FINISH
348SAV
5.7TBA
2SAV
2.4DAGS
254.2TFC
348.2DAGS
351.1AMH22 0751
150TFC
346.7TFA
351.1MGOINFILTRATION AT MANHOLE
0MWM
2MGOMAGNESIUM H.O. START 80%

Properties (6)

additional_info
SC205646
custom_field_two
3
customer
LACSD
datetime
2015-12-03T00:00:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false