Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 4, 2015, 07:31 AM
  • 22 0754_22 0753_20151203_234153.mp4

Date
12/03/2015
W/O
536652
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00821
PipeID
P17111
Time
11:31 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2878
Sewer Name
22 PUDDINGSTONE TRUNK, SECTS 1&2
City
SAN DIMAS, CA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
23
Purpose
Routine Assessment
Project
WO_536652_TV22057_NOV2015
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0754
Downstream MH
22 0753
Dir. of Survey
Downstream
Length Surveyed
269.1 ft.
Total Length
269.1 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
159
O&M Index
2
O&M Quick
2J00
O&M Rating
106
Overall Index
3
Overall Quick
Overall Rating
265
Pipe schematic from manhole 22 0754 to 22 0753
MH: 22 0754MH: 22 0753downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 07540 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. MGO - General Observation - MAGNESIUM H.O. START 20%2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start16.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"69.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6" - W/ SEVERELY LARGE OFFSET INSIDE LATERAL117.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"168.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"216.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"261.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"266 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish266.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish266.8 ft. MGO - General Observation - MAGNESIUM H.O. FINISH269.1 ft. AMH - Downstream Manhole, Survey Ends - 22 0753

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6" - W/ SEVERELY LARGE OFFSET INSIDE LATERAL

    69.2 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6" - W/ SEVERELY LARGE OFFSET INSIDE LATERAL

Observations (16)

DistanceCodeObservation
2MGOMAGNESIUM H.O. START 20%
269.1AMH22 0753
216.6TFC
0AMH22 0754
266SAV
0MWL
117.2TFC
16.5TFC
168.8TFA
2SAV
3.1DAGS
69.2TFAW/ SEVERELY LARGE OFFSET INSIDE LATERAL
0MWM
266.8DAGS
266.8MGOMAGNESIUM H.O. FINISH
261.2TFC

Properties (6)

additional_info
SC205646
custom_field_two
3
customer
LACSD
datetime
2015-12-03T23:31:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false