Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 3, 2015, 08:04 AM
  • 30 0153_30 0152_20151203_015526_.mpg

Date
12/03/2015
W/O
536532
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00878
PipeID
P17858
Time
12:04 AM
Certificate
12345
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2956
Sewer Name
30 SOUTH BAY CITIES MAIN TRUNK
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
07
Purpose
Routine Assessment
Project
WO_536532_TV30036_NOV2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Other
Height
10 in.
Upstream MH
30 0153
Downstream MH
30 0152
Dir. of Survey
Downstream
Length Surveyed
294.1 ft.
Total Length
294.1 ft.
Structural Index
3
Structural Quick
413E
Structural Rating
93
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
95
Pipe schematic from manhole 30 0153 to 30 0152
MH: 30 0153MH: 30 0152downstream0 ft. MGO - General Observation - CONNECTION AT MANHOLE 3 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 30 01538.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"13.8 ft. CM - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES22.9 ft. CM - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES39.2 ft. CM - Crack Multiple, from 06 to 09 o'clock, within 8 inches of joint: YES52.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"54.3 ft. CS - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES57.9 ft. CM - Crack Multiple, from 06 to 09 o'clock, within 8 inches of joint: YES, Start116.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"116.6 ft. RFL - Roots Fine Lateral, from 03 to 04 o'clock159.7 ft. CM - Crack Multiple, from 06 to 09 o'clock, within 8 inches of joint: YES, Finish163.6 ft. FM - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES185.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"186.8 ft. CM - Crack Multiple, from 06 to 12 o'clock, within 8 inches of joint: YES199.1 ft. CM - Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES219.9 ft. CM - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES223.8 ft. CM - Crack Multiple, from 02 to 06 o'clock, within 8 inches of joint: YES253.3 ft. RFL - Roots Fine Lateral, from 03 to 04 o'clock253.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"271.3 ft. CM - Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES279.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES294.1 ft. MGO - General Observation - CONNECTION AT MANHOLE 3 O'CLOCK294.1 ft. AMH - Downstream Manhole, Survey Ends - 30 0152

Observation photos (20)

  • General Observation - CONNECTION AT MANHOLE 3 O'CLOCK

    0 ft. - General Observation - CONNECTION AT MANHOLE 3 O'CLOCK

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    8.6 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

    13.8 ft. - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 06 to 09 o'clock, within 8 inches of joint: YES

    39.2 ft. - Crack Multiple, from 06 to 09 o'clock, within 8 inches of joint: YES

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    52.5 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

    54.3 ft. - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 06 to 09 o'clock, within 8 inches of joint: YES, Start

    57.9 ft. - Crack Multiple, from 06 to 09 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    116.6 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Roots Fine Lateral, from 03 to 04 o'clock

    116.6 ft. - Roots Fine Lateral, from 03 to 04 o'clock

  • Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    163.6 ft. - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    185.4 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Crack Multiple, from 06 to 12 o'clock, within 8 inches of joint: YES

    186.8 ft. - Crack Multiple, from 06 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES

    199.1 ft. - Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

    219.9 ft. - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 02 to 06 o'clock, within 8 inches of joint: YES

    223.8 ft. - Crack Multiple, from 02 to 06 o'clock, within 8 inches of joint: YES

  • Roots Fine Lateral, from 03 to 04 o'clock

    253.3 ft. - Roots Fine Lateral, from 03 to 04 o'clock

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    253.3 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

    271.3 ft. - Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    279.7 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • General Observation - CONNECTION AT MANHOLE 3 O'CLOCK

    294.1 ft. - General Observation - CONNECTION AT MANHOLE 3 O'CLOCK

Observations (26)

DistanceCodeObservation
54.3CS
116.6TB
223.8CM
199.1CM
159.7CM
39.2CM
116.6RFL
163.6FM
0MGOCONNECTION AT MANHOLE 3 O'CLOCK
22.9CM
0MWL
294.1MGOCONNECTION AT MANHOLE 3 O'CLOCK
219.9CM
253.3RFL
186.8CM
57.9CM
279.7CM
13.8CM
271.3CM
294.1AMH30 0152
8.6TF
185.4TF
253.3TF
0MWM
52.5TF
0AMH30 0153

Properties (6)

additional_info
SC205553
custom_field_two
3
customer
LACSD
datetime
2015-12-03T00:04:40-08:00
documentation
PRO PIPE
is_lateral_inspection
false