Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 8, 2015, 08:24 AM
  • 30 0131_30 0130_20151208_013646_.mp4

Date
12/08/2015
W/O
536532
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00878
PipeID
P17836
Time
12:24 AM
Certificate
12345
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
k2959
Sewer Name
30 SOUTH BAY CITIES MAIN TRUNK
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
07
Purpose
Routine Assessment
Project
WO_536532_TV30036_NOV2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Other
Height
18 in.
Upstream MH
30 0130
Downstream MH
30 0131
Dir. of Survey
Upstream
Length Surveyed
126.4 ft.
Total Length
126.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
413D
O&M Rating
74
Overall Index
3
Overall Quick
Overall Rating
74
Pipe schematic from manhole 30 0130 to 30 0131
MH: 30 0130MH: 30 0131upstream0 ft. AMH - Upstream Manhole, Survey Ends - 30 01311.4 ft. MGO - General Observation - CONNECTION AT MANHOLE3 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish9.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"26.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"57.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6"65.6 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"65.6 ft. RFL - Roots Fine Lateral, at 12 o'clock74.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"87.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"93.4 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"114.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"119.3 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start126.4 ft. AMH - Downstream Manhole, Survey Begins - 30 0130126.4 ft. MWM - Water Mark, 50 %of cross sectional area126.4 ft. MWL - Water Level, 20 %of cross sectional area

Observations (16)

DistanceCodeObservation
125MGOCONNECTION AT MANHOLE
33TB
60.8TB
123.4DAGS
7.1DAGS
51.7TFC
60.8RFL
116.9TFC
0AMH30 0130
0MWM
99.5TFC
0MWL
126.4AMH30 0131
39.3TFC
12.1TFC
68.9TF

Properties (6)

additional_info
SC205556
custom_field_two
4
customer
LACSD
datetime
2015-12-08T00:24:58-08:00
documentation
PRO PIPE
is_lateral_inspection
false