Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 1, 2020, 09:21 AM
  • B 1206_B 1205_06012020_023421.mp4

Date
06/01/2020
W/O
833527
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01125
PipeID
P13526
Time
2:21 AM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7680
Sewer Name
JOINT OUTFALL B - UNIT 6H
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
16
Purpose
Routine Assessment
Project
WO_833527_TV16042_JUN2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
B 1206
Downstream MH
B 1205
Dir. of Survey
Downstream
Length Surveyed
210.1 ft.
Total Length
210.1 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
123
O&M Index
2
O&M Quick
412H
O&M Rating
90
Overall Index
3
Overall Quick
Overall Rating
213
Pipe schematic from manhole B 1206 to B 1205
MH: B 1206MH: B 1205downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 12050 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. MGO - General Observation - MAG COATING THROUGHOUT2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start65.3 ft. TBI - Tap Break-In Intruding, at 10 o'clock, -, #v, within 8 inches of joint: NO, 6", 3"162.8 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"210.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish210.1 ft. AMH - Downstream Manhole, Survey Ends - B 1205210.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • General Observation - MAG COATING THROUGHOUT

    2 ft. - General Observation - MAG COATING THROUGHOUT

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.9 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Intruding, at 10 o'clock, -, #v, within 8 inches of joint: NO, 6", 3"

    65.3 ft. - Tap Break-In Intruding, at 10 o'clock, -, #v, within 8 inches of joint: NO, 6", 3"

Observations (11)

DistanceCodeObservation
0AMHB 1205
0MWM
65.3TBI
210.1DAGS
0MWL
2MGOMAG COATING THROUGHOUT
2DAGS
162.8TBA
210.1AMHB 1205
210.1SAP
2.9SAP

Properties (7)

additional_info
SC411272
custom_field_three
Aggregate visible
custom_field_two
3
customer
1
datetime
2020-06-01T02:21:40-07:00
documentation
PRO PIPE
is_lateral_inspection
false