Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 23, 2020, 03:57 AM
  • 02 2002_02 2001_06222020_211115.mp4

Date
06/22/2020
W/O
833628
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00260
PipeID
P04357
Time
8:57 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7737
Sewer Name
EAST COMPTON BOULEVARD RELIEF TRUNK #2
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_833628_TV02410_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
8 in.
Upstream MH
02 2002
Downstream MH
02 2001
Dir. of Survey
Downstream
Length Surveyed
310.4 ft.
Total Length
310.4 ft.
Structural Index
3
Structural Quick
413K
Structural Rating
183
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
183
Pipe schematic from manhole 02 2002 to 02 2001
MH: 02 2002MH: 02 2001downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 20020 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES7.1 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES11.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start305.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish310.4 ft. AMH - Downstream Manhole, Survey Ends - 02 2001

Observation photos (3)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    7.1 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    11.7 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0AMH02 2002
310.4AMH02 2001
0MWM
11.7CM
7.1CL
305.6CM
0MWL
2.1FM

Properties (8)

additional_info
SC411396
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2020-06-22T20:57:10-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
27557