- Date
- 06/11/2020
- W/O
- 833564`
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00722
- PipeID
- P15307
- Time
- 10:02 PM
- Certificate
- U-508-7069
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K7726
- Sewer Name
- EAST ARTESIA TRUNK, SECTS 1,2,3,&5
- City
- CERRITOS`
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 19
- Page No.
- 05
- Purpose
- Routine Assessment
- Project
- RFIR_WO_833564_TV19076_JUN2020
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 21 in.
- Width
- 21 in.
- Upstream MH
- 19 0118
- Downstream MH
- 19 0117
- Dir. of Survey
- Downstream
- Length Surveyed
- 476.6 ft.
- Total Length
- 476.6 ft.
- Structural Index
- 4
- Structural Quick
- 4131
- Structural Rating
- 7
- O&M Index
- 1
- O&M Quick
- 1100
- O&M Rating
- 1
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 8
Pipe schematic from manhole 19 0118 to 19 0117 Observation photos (4)

98 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

98 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

104.9 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

193.3 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"