Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 12, 2020, 05:02 AM
  • 19 0118_19 0117_06112020_221717.mp4

Date
06/11/2020
W/O
833564`
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00722
PipeID
P15307
Time
10:02 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7726
Sewer Name
EAST ARTESIA TRUNK, SECTS 1,2,3,&5
City
CERRITOS`
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_833564_TV19076_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
19 0118
Downstream MH
19 0117
Dir. of Survey
Downstream
Length Surveyed
476.6 ft.
Total Length
476.6 ft.
Structural Index
4
Structural Quick
4131
Structural Rating
7
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 19 0118 to 19 0117
MH: 19 0118MH: 19 0117downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 19 01180 ft. MWL - Water Level, 15 %of cross sectional area98 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start98 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start104.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish104.9 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start116.2 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish116.2 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish193.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"476.6 ft. AMH - Downstream Manhole, Survey Ends - 19 0117

Observation photos (4)

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    98 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    98 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    104.9 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    193.3 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (11)

DistanceCodeObservation
0MWM
98RFJ
476.6AMH19 0117
0AMH19 0118
193.3TB
104.9FM
98CM
116.2RFJ
104.8CM
116.2FM
0MWL

Properties (7)

additional_info
SC411384
custom_field_three
FRACTURE/ CRACK
custom_field_two
3
customer
1
datetime
2020-06-11T22:02:55-07:00
documentation
PROPIPE
is_lateral_inspection
false