Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 31, 2020, 10:42 AM
  • 18 0960_18 0959_7312020_040145.mp4

Date
07/31/2020
W/O
0839479
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00716
PipeID
P14808
Time
3:42 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1506R
Sewer Name
18 WORSHAM CREEK TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
10
Purpose
Maintenance Related
Project
20200728MDM_WORSHAM_CREEK_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
9.399999618530273 in.
Upstream MH
18 0960
Downstream MH
18 0959
Dir. of Survey
Downstream
Length Surveyed
356.8 ft.
Total Length
356.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3111
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 18 0960 to 18 0959
MH: 18 0960MH: 18 0959downstream0 ft. MGO - General Observation - MH CONN 3:00 ACTIVE0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:10AM7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN280.2 ft. RFC - Roots Fine Connection, from 02 to 03 o'clock, within 8 inches of joint: NO - 1%280.2 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: NO, 6" - ACTIVE-70% ROOTS285.5 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Active356.4 ft. MGO - General Observation - MH CONN 3:00 ACTIVE356.8 ft. AMH - Downstream Manhole, Survey Ends - 4:30AM

Observations (10)

DistanceCodeObservation
280.2RFC1%
0MGOMH CONN 3:00 ACTIVE
356.4MGOMH CONN 3:00 ACTIVE
356.8AMH4:30AM
280.2TBDACTIVE-70% ROOTS
0MWL
7TBOPEN
0MWM
0AMH4:10AM
285.5TBActive

Properties (6)

additional_info
ROOT EVALUATION ONLY
customer
LACSD
datetime
2020-07-31T03:42:59-07:00
documentation
MARTIN,OLIVER 111,SHADLER,BARR
is_lateral_inspection
false
lining
PVCP