Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 4, 2020, 08:23 AM
  • 02 1423_02 1422 _05042020_013853.mp4

Date
05/04/2020
W/O
829370
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00349
PipeID
P02994
Time
1:23 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7590
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
COMMERCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_829370_TV02220_MAY2020
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Width
60 in.
Upstream MH
02 1423
Downstream MH
02 1422
Dir. of Survey
Downstream
Length Surveyed
3 ft.
Total Length
3 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 02 1423 to 02 1422
MH: 02 1423MH: 02 1422downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 14230 ft. MWM - Water Mark, 45 %of cross sectional area2.1 ft. MGO - General Observation - MAG COATING ATTATCHED2.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES2.7 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES3 ft. MSA - Survey Abandoned - VIEW OF SIPHON DOWNLEG

Observation photos (3)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

    2.7 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES

    2.7 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - VIEW OF SIPHON DOWNLEG

    3 ft. - Survey Abandoned - VIEW OF SIPHON DOWNLEG

Observations (7)

DistanceCodeObservation
0MWL
0AMH02 1423
3MSAVIEW OF SIPHON DOWNLEG
2.1MGOMAG COATING ATTATCHED
2.7SAP
0MWM
2.7SRV

Properties (6)

additional_info
SC411149
custom_field_two
2
customer
LACSD
datetime
2020-05-04T01:23:04-07:00
documentation
PROPIPE
is_lateral_inspection
false