Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 4, 2020, 10:19 AM
  • 02 1407_02 1406 _05042020_033315.mp4

Date
05/04/2020
W/O
SC411149
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00349
PipeID
P02978
Time
3:19 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7590
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
COMMERCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_829370_TV02220_MAY2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
02 1407
Downstream MH
02 1406
Dir. of Survey
Downstream
Length Surveyed
185.5 ft.
Total Length
185.5 ft.
Structural Index
4
Structural Quick
5F3F
Structural Rating
296
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
296
Pipe schematic from manhole 02 1407 to 02 1406
MH: 02 1407MH: 02 1406downstream0 ft. MGO - General Observation - CONNECTION IN MH, 9 O' CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 14072.1 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start174 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - POSSBLE CONNECTION185 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish185 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 10"185.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish185.5 ft. AMH - Downstream Manhole, Survey Ends - 02 1406

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
185SRC
0MGOCONNECTION IN MH, 9 O' CLOCK
185.5SAP
0MWL
185TFC
2.1SRC
2.1SAP
185.5AMH02 1406
0MWM
0AMH02 1407
174TFPOSSBLE CONNECTION

Properties (5)

additional_info
SC411149
customer
LACSD
datetime
2020-05-04T03:19:29-07:00
documentation
PROPIPE
is_lateral_inspection
false