Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 5, 2020, 04:54 AM
  • 02 1401_02 1400_05042020_220110.mp4

Date
05/04/2020
W/O
SC411149
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00349
PipeID
P02972
Time
9:54 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7592
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_829370_TV02220_MAY2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
02 1401
Downstream MH
02 1400
Dir. of Survey
Downstream
Length Surveyed
160.3 ft.
Total Length
160.3 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 02 1401 to 02 1400
MH: 02 1401MH: 02 1400downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 14010 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area6.9 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start160.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish160.3 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish160.3 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK160.3 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK160.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish160.3 ft. AMH - Downstream Manhole, Survey Ends - 02 1400

Observation photos (3)

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.9 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
160.3SSS
0AMH02 1401
160.3SRC
6.9SRC
160.3MGOCONNECTION AT MH 9 O'CLOCK
0MWM
0MWL
160.3MGOCONNECTION AT MH 3 O'CLOCK
6.9SAP
6.9SSS
160.3SAP
160.3AMH02 1400

Properties (6)

additional_info
SC411150
custom_field_two
2
customer
LACSD
datetime
2020-05-04T21:54:02-07:00
documentation
PROPIPE
is_lateral_inspection
false