- Date
- 06/24/2020
- W/O
- 833616
- Weather
- Dry
- Operator/Surveyor
- J. BUENROSTRO
- Sewer ID
- Z00325
- PipeID
- P08282
- Time
- 1:51 AM
- Certificate
- U-715-07000770
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K7807
- Sewer Name
- JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
- City
- ROSEMEAD
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 15
- Purpose
- Routine Assessment
- Project
- RFIR_WO_833616_TV15244_JUN2020
- Sewer Type
- Gravity
- Material
- NRCP
- Shape
- Circular
- Height
- 24 in.
- Width
- 39 in.
- Upstream MH
- A 0372
- Downstream MH
- A 0371
- Dir. of Survey
- Downstream
- Length Surveyed
- 497.2 ft.
- Total Length
- 497.2 ft.
- Structural Index
- 3
- Structural Quick
- 3H2G
- Structural Rating
- 213
- O&M Index
- 2
- O&M Quick
- 2S00
- O&M Rating
- 196
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 409
Pipe schematic from manhole A 0372 to A 0371 Observation photos (4)

7.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

13.2 ft. - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO

31.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

40.4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start