Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 12, 2020, 06:53 AM
  • 19 0216B_19 0216A_06122020_000001.mp4

Date
06/11/2020
W/O
833528
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00718
PipeID
P26792
Time
11:53 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7728
Sewer Name
ARTESIA-CERRITOS TRUNK
City
artesia
Loc. details
Main Highway - Urban
Location Code
A
District
District 19
Page No.
04
Purpose
Routine Assessment
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Other
Height
12 in.
Upstream MH
19 0216B
Downstream MH
19 0216A
Dir. of Survey
Downstream
Length Surveyed
90.6 ft.
Total Length
90.6 ft.
Structural Index
3
Structural Quick
3C2B
Structural Rating
88
O&M Index
2
O&M Quick
2F00
O&M Rating
70
Overall Index
2
Overall Quick
Overall Rating
158
Pipe schematic from manhole 19 0216B to 19 0216A
MH: 19 0216BMH: 19 0216Adownstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 19 0216B2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start19.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"23.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN45.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN59.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN66.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN88 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish88 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish90.6 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish90.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish90.6 ft. AMH - Downstream Manhole, Survey Ends - 19 0216A90.6 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE

Observation photos (2)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
59.9TFOPEN
2SSS
2.1DAE
0MWL
45.6TFOPEN
2.2CM
88SSS
2DAGS
88DAGS
90.6DAE
0MWM
19.8TFC
90.6CM
90.6AMH19 0216A
0AMH19 0216B
23.2TFOPEN
90.6MGOCONN @ MH 3 O'CLOCK/ACTIVE
66.6TFOPEN

Properties (7)

additional_info
SC411386
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-06-11T23:53:56-07:00
documentation
PROPIPE
is_lateral_inspection
false