Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 12, 2020, 08:10 AM
  • 19 0295_19 0217_06122020_012143.mp4

Date
06/12/2020
W/O
833528
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00718
PipeID
P15187
Time
1:10 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7728
Sewer Name
ARTESIA-CERRITOS TRUNK
City
artesia
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_833528_TV19060_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
19 0217
Downstream MH
19 0295
Dir. of Survey
Upstream
Length Surveyed
243.8 ft.
Total Length
243.8 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
144
O&M Index
2
O&M Quick
312R
O&M Rating
195
Overall Index
2
Overall Quick
Overall Rating
339
Pipe schematic from manhole 19 0217 to 19 0295
MH: 19 0217MH: 19 0295upstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 19 02950 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE2.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish37.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"64.4 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: YES, 4" - BROKEN PIPE IN CONN64.4 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"95.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"101.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN112.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN138.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN178 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN180.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN239 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start239 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start241.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start243.8 ft. AMH - Downstream Manhole, Survey Begins - 19 0217243.8 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/UNKNOWN243.8 ft. MGO - General Observation - ROACHES @ MH243.8 ft. MWM - Water Mark, 30 %of cross sectional area243.8 ft. MWL - Water Level, 25 %of cross sectional area

Observation photos (3)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    4.8 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    179.4 ft. - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (23)

DistanceCodeObservation
104.9TFOPEN
243.8MGOCONN @ MH 9 O'CLOCK/ACTIVE
0AMH19 0217
243.8CM
243.8AMH19 0295
0MGOCONN @ MH 3 O'CLOCK/UNKNOWN
148.6TFA
0MGOROACHES @ MH
243.8DAE
179.4TBDBROKEN PIPE IN CONN
4.8DAE
243.8MGOCONN @ MH 3 O'CLOCK/ACTIVE
142.6TFOPEN
62.9TFOPEN
131.5TFOPEN
65.8TFOPEN
2DAGS
241DAGS
0MWM
205.9TFC
0MWL
179.4TS
4.8CM

Properties (7)

additional_info
SC411386
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-06-12T01:10:02-07:00
documentation
PROPIPE
is_lateral_inspection
false