Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 12, 2020, 07:06 AM
  • 19 0216_19 0215_06122020_001004.mp4

Date
06/12/2020
W/O
833528
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00718
PipeID
P15185
Time
12:06 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7728
Sewer Name
ARTESIA-CERRITOS TRUNK
City
artesia
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_833528_TV19060_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
19 0216
Downstream MH
19 0215
Dir. of Survey
Downstream
Length Surveyed
17 ft.
Total Length
17 ft.
Structural Index
2
Structural Quick
3223
Structural Rating
12
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
18
Pipe schematic from manhole 19 0216 to 19 0215
MH: 19 0216MH: 19 0215downstream0 ft. AMH - Upstream Manhole, Survey Begins - 19 02160 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"15 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish15 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish15.2 ft. MGO - General Observation - ABANDONED MH15.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish17 ft. AMH - Downstream Manhole, Survey Ends - 19 0215 ABANDONED MH

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
2DAGS
15DAGS
4.5CM
0AMH19 0216
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
0MWL
0MWM
10TFC
15SSS
0MGOROACHES @ MH
15.2MGOABANDONED MH
2SSS
15.2CM
17AMH19 0215 ABANDONED MH

Properties (7)

additional_info
SC411386
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-06-12T00:06:02-07:00
documentation
PROPIPE
is_lateral_inspection
false