Wastewater/Activity/PacpInspection/1.0Jun 5, 2020, 05:11 AM
  • 01 0555_01 0554_06042020_222246.mp4

Date
06/04/2020
W/O
833505
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00206
PipeID
P01044
Time
10:11 PM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7687
Sewer Name
CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
FLORENCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_833505_TV01243_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
12 in.
Upstream MH
01 0555
Downstream MH
01 0554
Dir. of Survey
Downstream
Length Surveyed
55.5 ft.
Total Length
55.5 ft.
Structural Index
3
Structural Quick
4139
Structural Rating
51
O&M Index
2
O&M Quick
2A00
O&M Rating
20
Overall Index
2
Overall Quick
Overall Rating
71
Pipe schematic from manhole 01 0555 to 01 0554
MH: 01 0555MH: 01 0554downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 6 O' CLOCK/ACTIVE0 ft. MGO - General Observation - ROACHES @ MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 01 05552 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES34.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"53 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish53.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish53.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish55.5 ft. MGO - General Observation - ROACHES @ MANHOLE55.5 ft. AMH - Downstream Manhole, Survey Ends - 01 055455.5 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE

Observation photos (5)

  • General Observation - ROACHES @ MANHOLE

    0 ft. - General Observation - ROACHES @ MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    5.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • General Observation - ROACHES @ MANHOLE

    55.5 ft. - General Observation - ROACHES @ MANHOLE

Observations (16)

DistanceCodeObservation
2DAGS
0MWM
0MWL
34.5TFC
0MGOCONN @ MH 6 O' CLOCK/ACTIVE
53SSS
0MGOROACHES @ MANHOLE
0AMH01 0555
53.2CM
55.5MGOROACHES @ MANHOLE
55.5AMH01 0554
2CM
2SSS
53.2DAGS
55.5MGOCONN @ MH 9 O'CLOCK/ACTIVE
5.7FM

Properties (7)

additional_info
SC411279
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2020-06-04T22:11:56-07:00
documentation
PRO PIPE
is_lateral_inspection
false