Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 5, 2020, 05:23 AM
  • 01 0554_01 0553_06042020_223736.mp4

Date
06/04/2020
W/O
833505
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00206
PipeID
P01043
Time
10:23 PM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7687
Sewer Name
CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
FLORENCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_833505_TV01243_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
12 in.
Upstream MH
01 0554
Downstream MH
01 0553
Dir. of Survey
Downstream
Length Surveyed
296.7 ft.
Total Length
296.7 ft.
Structural Index
3
Structural Quick
4K3K
Structural Rating
522
O&M Index
2
O&M Quick
2K00
O&M Rating
118
Overall Index
3
Overall Quick
Overall Rating
640
Pipe schematic from manhole 01 0554 to 01 0553
MH: 01 0554MH: 01 0553downstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 05540 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MANHOLE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start63 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"81.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"125.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"149.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN194.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"257.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"260.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"294 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish294 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish294.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish294.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish296.7 ft. MGO - General Observation - ROACHES @ MANHOLE296.7 ft. AMH - Downstream Manhole, Survey Ends - 01 0553296.7 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: YES, 6"296.7 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE

Observation photos (3)

  • General Observation - ROACHES @ MANHOLE

    0 ft. - General Observation - ROACHES @ MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (24)

DistanceCodeObservation
149.7TFAOPEN
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
294.9FM
294SSS
2DAGS
4.2FM
2CM
257.6TFC
296.7MGOROACHES @ MANHOLE
296.7AMH01 0553
0MWL
260.6TFC
294.9DAGS
2SSS
125.8TFC
0AMH01 0554
0MWM
63TFC
81.3TFC
296.7TFA
0MGOROACHES @ MANHOLE
296.7MGOCONN @ MH 9 O'CLOCK/ACTIVE
294CM
194.8TFC

Properties (7)

additional_info
SC411279
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2020-06-04T22:23:27-07:00
documentation
PRO PIPE
is_lateral_inspection
false