Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 5, 2020, 08:32 AM
  • 01 0548_01 0547_06052020_014054.mp4

Date
06/05/2020
W/O
833505
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00206
PipeID
P01037
Time
1:32 AM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7687
Sewer Name
CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
FLORENCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_833505_TV01243_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
15 in.
Upstream MH
01 0547
Downstream MH
01 0548
Dir. of Survey
Upstream
Length Surveyed
61.4 ft.
Total Length
61.4 ft.
Structural Index
3
Structural Quick
3A2A
Structural Rating
55
O&M Index
2
O&M Quick
2A00
O&M Rating
24
Overall Index
2
Overall Quick
Overall Rating
79
Pipe schematic from manhole 01 0547 to 01 0548
MH: 01 0547MH: 01 0548upstream0 ft. MGO - General Observation - CONN @ MH 10 O'CLOCK/0 ft. MGO - General Observation - CONN @ MH 4 O' CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 01 05480.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish0.1 ft. MGO - General Observation - ROACHES @ MANHOLE0.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish52.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start59.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start59.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start61.4 ft. MGO - General Observation - CONN @ MH 9 O' CLOCK/ACTIVE61.4 ft. MGO - General Observation - ROACHES @ MANHOLE61.4 ft. MWM - Water Mark, 30 %of cross sectional area61.4 ft. MWL - Water Level, 25 %of cross sectional area61.4 ft. MGO - General Observation - CONN @ MH 3 O' CLOCK/UNKNOWN61.4 ft. AMH - Downstream Manhole, Survey Begins - 01 0547

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ROACHES @ MANHOLE

    61.3 ft. - General Observation - ROACHES @ MANHOLE

Observations (16)

DistanceCodeObservation
0MGOCONN @ MH 9 O' CLOCK/ACTIVE
0MGOROACHES @ MANHOLE
59SSS
2DAGS
2SSS
61.4MGOCONN @ MH 10 O'CLOCK/
8.5CM
61.3DAGS
0MWM
61.4MGOCONN @ MH 4 O' CLOCK
61.3MGOROACHES @ MANHOLE
0MWL
61.4AMH01 0548
61.3CM
0MGOCONN @ MH 3 O' CLOCK/UNKNOWN
0AMH01 0547

Properties (7)

additional_info
SC411279
custom_field_three
MULTIPLE FRACTURES
custom_field_two
3
customer
1
datetime
2020-06-05T01:32:34-07:00
documentation
PRO PIPE
is_lateral_inspection
false