- Date
- 06/05/2020
- W/O
- 833505
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00206
- PipeID
- P01031
- Time
- 2:36 AM
- Certificate
- U-111-11880
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K7687
- Sewer Name
- CROCKETT BOULEVARD-GLEN AVENUE TRUNK
- City
- FLORENCE
- Loc. details
- Alley
- Location Code
- H
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 07
- Purpose
- Routine Assessment
- Project
- RFIR_WO_833505_TV01243_JUN2020
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 12 in.
- Width
- 15 in.
- Upstream MH
- 01 0543
- Downstream MH
- 01 0542
- Dir. of Survey
- Downstream
- Length Surveyed
- 31 ft.
- Total Length
- 31 ft.
- Structural Index
- 3
- Structural Quick
- 3525
- Structural Rating
- 25
- O&M Index
- 2
- O&M Quick
- 4125
- O&M Rating
- 14
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 39
Pipe schematic from manhole 01 0543 to 01 0542 Observation photos (5)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

8 ft. - Surface Corrosion Metal Pipe, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

8 ft. - Material Change, Cast Iron

24.4 ft. - Material Change, Vitrified clay pipe

31 ft. - General Observation - CONN @ MH 4 O'CLOCK/ACTIVE