Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 1, 2020, 09:33 AM
  • 22 0667_22 0666_06012020_030347.mp4

Date
06/01/2020
W/O
828889
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00827
PipeID
P17016
Time
2:33 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7636
Sewer Name
22 SUNFLOWER TRUNK
City
SAN DIMAS
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
22
Purpose
Routine Assessment
Project
WO_828889_TV22063_MAY2020
Sewer Type
Gravity
Material
NRCP
Shape
Square
Height
15 in.
Width
15 in.
Upstream MH
22 0666
Downstream MH
22 0667
Dir. of Survey
Upstream
Length Surveyed
177.8 ft.
Total Length
177.8 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
105
O&M Index
2
O&M Quick
2F00
O&M Rating
72
Overall Index
2
Overall Quick
Overall Rating
177
Pipe schematic from manhole 22 0666 to 22 0667
MH: 22 0666MH: 22 0667upstream0 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish0 ft. MSA - Survey Abandoned - OBSTACLE0 ft. OBZ - Obstacles Other, 5 %of cross sectional area, from 05 to 07 o'clock - UNKNOW0 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish23.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"28.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 4"94.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"99.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4", 4"160.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"165.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"174.7 ft. MGO - General Observation - MAG COATING ATTATCHED174.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start174.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start177.8 ft. MWM - Water Mark, 20 %of cross sectional area177.8 ft. AMH - Downstream Manhole, Survey Begins - 22 0666177.8 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    3.1 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
177.8DAE
3.1MGOMAG COATING ATTATCHED
0MWM
78.1TFC
17.2TFC
0AMH22 0666
83.2TFC
149.2TFC
0MWL
177.8MSAOBSTACLE
177.8OBZUNKNOW
3.1SAP
154.1TFC
3.1DAE
12.4TFC
177.8SAP

Properties (6)

additional_info
SC411186
custom_field_two
5
customer
LACSD
datetime
2020-06-01T02:33:12-07:00
documentation
PROPIPE
is_lateral_inspection
false