Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 29, 2020, 09:12 AM
  • 22 0663A_22 0663_05292020_025647.mp4

Date
05/29/2020
W/O
828889
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00827
PipeID
P17012
Time
2:12 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7634
Sewer Name
22 SUNFLOWER TRUNK
City
SAN DIMAS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
22
Purpose
Routine Assessment
Project
WO_828889_TV22063_MAY2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0663
Downstream MH
22 0663A
Dir. of Survey
Upstream
Length Surveyed
374 ft.
Total Length
374 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
1
O&M Quick
2118
O&M Rating
10
Overall Index
1
Overall Quick
Overall Rating
13
Pipe schematic from manhole 22 0663 to 22 0663A
MH: 22 0663MH: 22 0663Aupstream0 ft. AMH - Upstream Manhole, Survey Ends - 22 0663A0.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0.5 ft. LR - Alignment Right, 5 %, Finish0.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, at 04 o'clock, , within 8 inches of joint: YES, Finish10.1 ft. LR - Alignment Right, 5 %, Start13.4 ft. LL - Alignment Left, 10 %, Finish43.6 ft. LL - Alignment Left, 10 %, Start57.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"64 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"125 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"129.8 ft. TFB - Tap Factory Made Abandoned, at 02 o'clock, -, within 8 inches of joint: NO, 4"143.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4"170.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"180.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"216.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"222.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4"256.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"286.9 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 4"323.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"328.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"362.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start371.6 ft. MGO - General Observation - MAG COATING ATTATCHED371.6 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, at 04 o'clock, , within 8 inches of joint: YES, Start374 ft. MWL - Water Level, 20 %of cross sectional area374 ft. MWM - Water Mark, 20 %of cross sectional area374 ft. AMH - Downstream Manhole, Survey Begins - 22 0663

Observation photos (2)

  • Deposits Attached Encrustation, 5 %of cross sectional area, at 04 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, at 04 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (26)

DistanceCodeObservation
45.7TF
157.7TFC
249TFC
87.1TB
0MWL
316.1TF
151.8TB
363.9LR
330.4LL
373.5SAP
244.2TFB
0MWM
2.4MGOMAG COATING ATTATCHED
373.5LR
193.1TFC
203.5TFC
373.5DAE
50.7TFC
230.2TB
11.2SAP
0AMH22 0663
2.4DAE
374AMH22 0663A
117.4TF
360.6LL
310TF

Properties (6)

additional_info
SC411184
custom_field_two
3
customer
LACSD
datetime
2020-05-29T02:12:01-07:00
documentation
PROPIPE
is_lateral_inspection
false