Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 22, 2020, 11:13 AM
  • H 0679_H 0678_06222020_041740.mp4

Date
06/22/2020
W/O
833503
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00941
PipeID
P11086
Time
4:13 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7803
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
PICO RIVERA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_833503_TV18106_JUN2020
Sewer Type
Siphon
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
H 0678
Downstream MH
H 0679
Dir. of Survey
Upstream
Length Surveyed
3.4 ft.
Total Length
3.4 ft.
Structural Index
2
Structural Quick
2111
Structural Rating
3
O&M Index
4
O&M Quick
4200
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole H 0678 to H 0679
MH: H 0678MH: H 0679upstream0 ft. SRI - Surface Roughness Increased, from 09 to 03 o'clock, within 8 inches of joint: YES0 ft. MSA - Survey Abandoned - VIEW OF SIPHON UPLEG0.2 ft. LU - Alignment Up, 45 %1.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES3.4 ft. MWL - Water Level, 100 %of cross sectional area3.4 ft. MWM - Water Mark, 100 %of cross sectional area3.4 ft. AMH - Downstream Manhole, Survey Begins - H 0678

Observation photos (1)

  • Surface Roughness Increased, from 09 to 03 o'clock, within 8 inches of joint: YES

    3.4 ft. - Surface Roughness Increased, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (7)

DistanceCodeObservation
0MWL
2SSS
3.4SRI
0MWM
0AMHH 0678
3.2LU
3.4MSAVIEW OF SIPHON UPLEG

Properties (6)

additional_info
SC411613
custom_field_two
5
customer
1
datetime
2020-06-22T04:13:33-07:00
documentation
PROPIPE
is_lateral_inspection
false