Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2020, 08:17 AM
  • 08 0171_08 0170_06242020_013017.mp4

Date
06/24/2020
W/O
833499
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00009
PipeID
P00228
Time
1:17 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7743
Sewer Name
GRACE STREET TRUNK, SECTION 1
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_833499_TV08166_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
18 in.
Upstream MH
08 0171
Downstream MH
08 0170
Dir. of Survey
Downstream
Length Surveyed
329.5 ft.
Total Length
329.5 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
325
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
331
Pipe schematic from manhole 08 0171 to 08 0170
MH: 08 0171MH: 08 0170downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 01710 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start22.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start39.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN90.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"137.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN193.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN241.8 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES244.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN286.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN295.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"327 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish327 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish329.5 ft. AMH - Downstream Manhole, Survey Ends - 08 0170329.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES, Start

    22.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 05 o'clock,  , within 8 inches of joint: YES

    241.8 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
90.6TFC
286.9TFOPEN
244.6TFOPEN
327SSS
0MWM
22.4DAGS
3CM
0AMH08 0171
295.4TFC
137.7TFOPEN
39.7TFOPEN
2SSS
241.8DAGS
0MWL
327DAGS
329.5AMH08 0170
193.6TFOPEN
329.5CM

Properties (7)

additional_info
SC411752
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-06-24T01:17:36-07:00
documentation
PROPIPE
is_lateral_inspection
false