Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2020, 04:26 AM
  • C 0453_C 0452_06232020_221916.mp4

Date
06/23/2020
W/O
833637
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00128
PipeID
P09658
Time
9:26 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7741
Sewer Name
JOINT OUTFALL C - UNIT 5A REPLACEMENT
City
LONG BEACH
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_833637_TV03175_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
12 in.
Upstream MH
C 0453
Downstream MH
C 0452
Dir. of Survey
Downstream
Length Surveyed
623.2 ft.
Total Length
623.2 ft.
Structural Index
3
Structural Quick
3X2X
Structural Rating
623
O&M Index
2
O&M Quick
413C
O&M Rating
333
Overall Index
2
Overall Quick
Overall Rating
956
Pipe schematic from manhole C 0453 to C 0452
MH: C 0453MH: C 0452downstream0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 04532 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start3.9 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start63.7 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish63.8 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 20 %, within 8 inches of joint: YESR, Start107.8 ft. CM - Crack Multiple, from 09 to 10 o'clock, within 8 inches of joint: YES176 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 20 %, within 8 inches of joint: YESR, Finish523.6 ft. RFJ - Roots Fine Joint, from 12 to 04 o'clock, within 8 inches of joint: YES582.6 ft. RFB - Roots Fine Barrell, from 02 to 05 o'clock584.3 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES620.5 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES620.5 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish620.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish621 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish623.2 ft. MGO - General Observation - CONN @ MH 9 O' CLOCK/ACTIVE623.2 ft. AMH - Downstream Manhole, Survey Ends - C 0452

Observation photos (9)

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    3.9 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Roots Medium Joint, from 08 to 04 o'clock, 20 %, within 8 inches of joint: YESR, Start

    63.8 ft. - Roots Medium Joint, from 08 to 04 o'clock, 20 %, within 8 inches of joint: YESR, Start

  • Crack Multiple, from 09 to 10 o'clock, within 8 inches of joint: YES

    107.8 ft. - Crack Multiple, from 09 to 10 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 12 to 04 o'clock, within 8 inches of joint: YES

    523.6 ft. - Roots Fine Joint, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Barrell, from 02 to 05 o'clock

    582.6 ft. - Roots Fine Barrell, from 02 to 05 o'clock

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

    584.3 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

    620.5 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
176RMJ
621SSS
0MWM
620.5RFJ
0MWL
107.8CM
584.3RFJ
2SSS
3.9DAGS
2RFJ
0AMHC 0453
63.7RFJ
623.2MGOCONN @ MH 9 O' CLOCK/ACTIVE
620.5DAGS
523.6RFJ
2CM
63.8RMJ
623.2AMHC 0452
582.6RFB
620.5CM

Properties (8)

additional_info
SC411400
custom_field_three
CRACKS/ ROOTS/ GREASE
custom_field_two
3
customer
1
datetime
2020-06-23T21:26:25-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
31644